Battery runtime

Estimate runtime or the capacity needed for a target runtime.

Electrical arithmetic only. This does not select installation ampacity, circuit protection, or establish code compliance.

Options
%

%

Starting values are examples. Replace them with your measurements.

Result

Enter your values, then calculate.

Calculation method

Runtime = rated Ah × usable fraction × efficiency / load current.

Method 2026-10-05.1. Independent review pending.

Estimating battery runtime

Battery runtime depends on usable capacity and the average load, not just the capacity printed on the case. Use the current mode when the load is known in amps. Use the power mode when you know watts and battery voltage. The capacity mode works backward from a required runtime.

Use an average over the operating cycle

A device that cycles on and off does not draw its peak current continuously. Include standby time and other loads when estimating the average. Keep startup demand separate: a battery may have enough stored energy but still be unable to supply a brief high-current event.

Why measured runtime may differ

The usable-capacity and efficiency inputs are allowances you supply. This arithmetic model does not predict aging, temperature effects, discharge-rate behavior, or the exact shutdown voltage of your equipment. Use representative discharge data when runtime matters to the design.

Relating amp-hours to watt-hours

Amp-hours describe charge, while watt-hours describe energy. Multiplying nominal voltage by amp-hour capacity gives an approximate nominal energy figure. A 12 V, 20 Ah battery corresponds to 240 Wh on that basis. At a steady 60 W load, ideal runtime is four hours before usable-capacity and efficiency allowances. This example is arithmetic, not a promise about a particular battery's discharge behavior.

Choose a load estimate that includes every device powered by the battery, including conversion equipment and standby consumers where applicable. A constant-power load may draw increasing current as battery voltage falls, so a single nominal-current assumption can miss that behavior. To compare batteries at different voltages, work in energy rather than amp-hours alone. The required-capacity mode can provide a starting size for a runtime target, but check the candidate battery's discharge curves and equipment cutoff conditions. Keep enough margin for the operating conditions instead of interpreting decimal runtime output as minute-by-minute accuracy.

Formula

Runtime = rated Ah × usable fraction × efficiency / load current.

Embed this calculator

Paste this HTML into a page that accepts iframes. The widget uses the same calculation method and keeps its warnings visible. No account is needed.

Adjust the height to suit your page. Saved work is not available inside the widget. Preview addresses are temporary; use the permanent site address for a published embed.